	Product use:RIP condenser transformer/reactor bushings are mainly used in power transformers/reactors, working as the current carrying conductors for pulling in or drawing high, medium and low voltage side current of transformers/reactors, and playing a role of insulation for oil tank shell of transformers/reactors.
	Service conditions:
	· Altitude: 1000m (products can be designed according to altitude correction coefficient if  altitude is higher than 1000m)
	· Ambient air temperature: -45℃- +60℃
	· Installation angle: arbitrarily
	Product structure: it is mainly composed of conducting pole, RIP capacitor core, high temperature liquid silicone rubber composite external insulation, equalizing ball, test tap, fittings, etc.
	 
	Advantages of bushings:
	Ø Unique resin system and special buffer strips
	Ø The most advanced production equipment of the world guarantee the better electrical properties, heat-resistance and mechanical properties of RIP bushings series.
	Ø The lower weight and smaller volume make it easy for transportation, erection and maintenance.
	         Ø Oil-free and gas-free design is more environmentally friendly, no risk of explosion;
	 
	    Ø Excellent performance ensures long-term stable online operation.
 
                              
	Description of product type
	
	 
	a Product type code
	· BRFG Composite insulated RIP condenser transformer bushing
	·BRCG Porcelain insulated RIP condenser transformer bushing
	·BRQG Oil- SF6 RIP condenser transformer bushing
	·BROG Oil- oil RIP condenser transformer bushing
	· CRFG Composite insulated RIP condenser wall bushing
	·CRCG Porcelain insulated RIP condenser wall bushing
	· DRFG Composite insulated RIP condenser generator bushing
	·GRFG Composite insulated RIP condenser GIS outlet line bushing
	b Structural features code
	 L  means it can be equipped with current transformers; no L means it can not be equipped with current transformers.
	c Classification code
	DC bushings are indicated with the letter Z; AC bushings are not expressed.
	d Way of current carrying
	 1-Direct type;2-Cable through type
	 
	TableⅠ Electrical performance table of oil - air dry-type condenser transformer/reactor bushings
	 
	
		
			| 
				 
					Systemic nominal voltage Un  kV 
			 | 
			
				 
					35 
			 | 
			
				 
					66 
			 | 
			
				 
					110 
			 | 
			
				 
					132 
			 | 
			
				 
					150 
			 | 
			
				 
					220 
			 | 
			
				 
					330 
			 | 
			
				 
					420 
			 | 
			
				 
					500 
			 | 
		
		
			| 
				 
					Rated voltage Ur  kV 
			 | 
			
				 
					40.5 
			 | 
			
				 
					72.5 
			 | 
			
				 
					126 
			 | 
			
				 
					145 
			 | 
			
				 
					170 
			 | 
			
				 
					252 
			 | 
			
				 
					363 
			 | 
			
				 
					420 
			 | 
			
				 
					550 
			 | 
		
		
			| 
				 
					Maximum working phase voltage for equipment  Ur/   kV 
			 | 
			
				 
					23.5 
			 | 
			
				 
					42 
			 | 
			
				 
					73 
			 | 
			
				 
					84 
			 | 
			
				 
					98.5 
			 | 
			
				 
					146 
			 | 
			
				 
					210 
			 | 
			
				 
					242 
			 | 
			
				 
					317 
			 | 
		
		
			| 
				 
					60s Power frequency withstand voltage 
			 | 
			
				 
					Dry  kV (r.m.s) 
			 | 
			
				 
					95 
			 | 
			
				 
					155 
			 | 
			
				 
					255 
			 | 
			
				 
					305 
			 | 
			
				 
					355 
			 | 
			
				 
					505 
			 | 
			
				 
					625 
			 | 
			
				 
					695 
			 | 
			
				 
					870 
			 | 
		
		
			| 
				 
					Wet  kV(r.m.s) 
			 | 
			
				 
					80 
			 | 
			
				 
					140 
			 | 
			
				 
					230 
			 | 
			
				 
					275 
			 | 
			
				 
					325 
			 | 
			
				 
					460 
			 | 
			
				 
					535 
			 | 
			
				 
					680 
			 | 
			
				 
					790 
			 | 
		
		
			| 
				 
					Lightning impulse withstand voltage 
			 | 
			
				 
					Full wave kV (peak) 
			 | 
			
				 
					200 
			 | 
			
				 
					325 
			 | 
			
				 
					550 
			 | 
			
				 
					650 
			 | 
			
				 
					750 
			 | 
			
				 
					1050 
			 | 
			
				 
					1175 
			 | 
			
				 
					1425 
			 | 
			
				 
					1800 
			 | 
		
		
			| 
				 
					Chopped wave  kV (peak) 
			 | 
			
				 
					- 
			 | 
			
				 
					- 
			 | 
			
				 
					635 
			 | 
			
				 
					750 
			 | 
			
				 
					865 
			 | 
			
				 
					1210 
			 | 
			
				 
					1495 
			 | 
			
				 
					1639 
			 | 
			
				 
					2070 
			 | 
		
		
			| 
				 
					Switching impulse withstand voltage (dry or wet)  kV (peak) 
			 | 
			
				 
					- 
			 | 
			
				 
					- 
			 | 
			
				 
					- 
			 | 
			
				 
					- 
			 | 
			
				 
					- 
			 | 
			
				 
					850 
			 | 
			
				 
					950 
			 | 
			
				 
					1050 
			 | 
			
				 
					1300 
			 | 
		
		
			| 
				 
					Dielectric loss % 
			 | 
			
				 
					Added value (not more than) 
			 | 
			
				 
					1.05Ur/  - Ur: 0.1 
			 | 
		
		
			| 
				 
					Maximum value 
			 | 
			
				 
					40.5kV - 363kV 
			 | 
			
				 
					0.6, measured at the voltage of 1.05Ur/  
			 | 
		
		
			| 
				 
					420kV - 550kV 
			 | 
			
				 
					0.5, measured at the voltage of 1.05Ur/  
			 | 
		
		
			| 
				 
					Partial discharge at the voltage of Ur (not more than)   pC 
			 | 
			
				 
					10 
			 | 
		
	
	 
	 
	Schematic diagram of  72.5kV and 126kV dry-type condenser transformer bushing 
	 
	
	Main dimensions of 72.5kV and 126kV dry-type condenser transformer bushings
	                                                                                                                                        Unit:mm
	 
	
	 
	 
	Schematic diagram of  145kV and 170kV dry-type condenser transformer bushing
	
	 
	 Main dimensions of 145kV and 170kV dry-type condenser transformer bushings
	                                                                                                                                            Unit:mm
	 
	
	 
	 
	Schematic diagram of  252kV and 550kV dry-type condenser transformer bushing
	 
	
	 
	Main dimensions of 252kV dry-type condenser transformer bushings
	                                                                        Unit:mm
	
	 
	 
	 
	Main dimensions of 550kV dry-type condenser transformer bushings
	                                                                                                                                          Unit:mm
	 
	